kVA to kW Calculator for Business Supplies and Generators
Updated 28 October 2026 · Renewable Energy for Businesses
kVA, kW and amps calculator
UK nominal voltages: 230 V single-phase and 400 V between phases on a three-phase supply. Results are arithmetic for planning; an electrician or the network operator confirms what a site can take. Nothing you enter is stored or sent unless you send it through the form.
What do kVA, kW and power factor mean?
kW is real power, the part that turns a motor or heats water. kVA is apparent power, which the IET defines as voltage multiplied by current, ignoring the phase angle between them. Power factor is kW divided by kVA, a ratio from 0 to 1 in both the IET's and CIBSE Journal's definitions.
- kW = kVA × power factor. 200 kVA at 0.9 is 180 kW.
- kVA = kW ÷ power factor. A 180 kW load at 0.9 needs 200 kVA.
Below a power factor of 1, part of the current carries reactive power, which the IET says does no direct work; the power factor correction guide covers when that is charged.
| Power factor | kW from 100 kVA | kVA needed for 100 kW |
|---|---|---|
| 1.0 | 100 | 100 |
| 0.95 | 95 | 105 |
| 0.9 | 90 | 111 |
| 0.8 | 80 | 125 |
Calculated from the two formulas and rounded.
How do amps turn into kVA on a UK supply?
Multiply amps by volts and divide by 1,000. Under regulation 27 of the Electricity Safety, Quality and Continuity Regulations 2002, the declared low-voltage supply is 230 V from phase to neutral unless a different figure is agreed in writing, and an IET Wiring Matters article gives 400 V between the lines of a three-phase system.
- Single-phase: kVA = 230 × amps ÷ 1,000, so 100 A is 23 kVA.
- Three-phase: kVA = 1.732 × 400 × amps per phase ÷ 1,000, where 1.732 is the square root of 3. Adding up three phases at 230 V each lands within half a per cent of the same answer.
National Grid Electricity Distribution (NGED) rates its small commercial connection at up to 100 A per phase and 69 kVA, which is what the three-phase sum gives for 100 A. Above that line a supply generally moves to CT metering, through current transformers rather than directly through the meter. A 150 kVA three-phase supply carries about 217 A on each phase, not in total; the three-phase supply guide covers balancing the phases.
Which power factor should you use?
- Your own, from half-hourly data or a logger.
- 0.95 to test for reactive charges. The IET describes a common method that charges when an installation's power factor averages below 0.95 over a half-hour.
- 0.8 for generators. Atlas Copco, which makes the QAS range of diesel generators, says a standard power factor of 0.8 is assumed for most generators.
The Energy Saving Trust's fleet toolkit uses 95% for its example depot, where a 150 kVA supply gives a maximum site demand of 142.5 kW. Erring low on power factor overstates the kVA, the safer mistake when checking headroom.
Where does a business find its agreed capacity?
On a half-hourly metered supply it is the Maximum Import Capacity (MIC). NGED says the MIC is measured in kVA, agreed with the network operator and stated in the connection agreement where applicable, and Electricity North West allocates a standard MIC to every half-hourly metered customer.
Electricity North West says the supplier's bill shows the kVA used each month, and defines maximum demand as the most power drawn at any one time in a billing period. Smaller supplies are often rated in amps per phase instead, which the formulas above convert.
What happens when demand goes over the agreed capacity?
Electricity North West says maximum demand should not exceed the MIC and that excess capacity charges apply if it does. Under DCP161, a change to the Distribution Connection and Use of System Agreement, capacity above the MIC has been charged at a higher rate from April 2018. Electricity North West passes the charge to the supplier, and it appears on the monthly bill.
Trimming the MIC too far is risky too: NGED fixes a reduced MIC for 12 months, and capacity given up may be required by other customers in the area. Size it from a year of peaks plus known new load.
Why are generators and transformers rated in kVA?
Because they carry the full current, whatever the load's power factor. Atlas Copco says generators are rated in kVA because the unit accounts for both active and reactive power. CIBSE Journal explains that a reactive load raises the volts × amps demand and the energy flowing in the conductors, altering the effective capacity of the distribution system, and that correcting it can allow a smaller distribution cable. A transformer carries the same current, so it is rated in kVA for the same reason.
Aggreko says a 1,000 kVA generator should not automatically be described as a 1 MW generator; its own 1,000 kVA containerised set has a published prime rating of 830 kW.
How do you estimate maximum demand for new equipment?
The IET says the installation's designer is responsible for assessing maximum demand: the sum of the connected loads multiplied by a factor for diversity, an allowance for equipment that does not all run flat out at once.
- Measure the present peak from the bill or a logger. The IET favours logging over an extended period, because a short log misses seasonal variation.
- Convert new nameplates to kVA. For example, 60 kW of motors at a power factor of 0.8 adds 75 kVA, not 60.
- Ask before buying. NGED says an electrician should be able to calculate maximum power, and SSEN needs the required kVA for any change in load at a commercial property.
The guide to electrifying a business site shows how chargers and heat pumps fit existing headroom, and the connections guide covers applying for more. The cost guide sets out what drives the price of a solar, battery or heat pump project, and you can send an enquiry through the site's form.
Sources
- legislation.gov.uk, The Electricity Safety, Quality and Continuity Regulations 2002, regulation 27; checked 28 October 2026.
- IET: Wiring Matters, Myth Busters (May 2018) and How embedded solar PV can affect the power factor of an installation (September 2025); Electrical diversity and load curtailment webinar questions and answers; checked 28 October 2026.
- CIBSE Journal, Module 41: Power quality for building electrical supplies (June 2012); checked 28 October 2026.
- Electricity North West, Upgrade or reduce your supply; National Grid Electricity Distribution, Changing your electricity load and Connection for a single commercial property up to 69kVA; SSEN, Increase or decrease your electricity supply; checked 28 October 2026.
- Energy Saving Trust, Fleet decarbonisation toolkit: charging profiles; checked 28 October 2026.
- Manufacturers' own pages: Atlas Copco, How to size a generator and QAS diesel generators; Aggreko UK, 1000 kVA containerised diesel generator and kVA vs kW; checked 28 October 2026.
Guides on this topic
Common questions
What does kVA stand for?
Kilovolt-ampere, the unit of apparent power. Aggreko gives one kVA as equivalent to 1,000 volt amps, and Electricity North West describes kVA as the total amount of power in use in a system.
How many kW is 100 kVA?
It depends on the power factor. 100 kVA is 80 kW at 0.8, 85 kW at 0.85 and 95 kW at 0.95, and only at a power factor of 1 are the two numbers the same. Use your site's own power factor when you know it.
How do I convert kVA to amps on a three-phase supply?
Multiply the kVA by 1,000 and divide by 1.732 × 400, which gives the current on each phase. 100 kVA comes to about 144 A per phase and 69 kVA to about 100 A. On a single-phase supply divide by 230 instead, so 23 kVA is 100 A.
Is kVA the same as kW?
No, unless the power factor is 1. kVA counts all the current the supply carries, including the part carrying reactive power, while kW counts only the power doing work. A half-hourly site's Maximum Import Capacity is set in kVA, so convert equipment ratings in kW before comparing.