Communal Heating: The Metering and Billing Rules for Landlords
Updated 23 October 2026 · Renewable Energy for Businesses
Want to cut what your site uses and pays for energy?
Request a quoteA landlord that supplies heat to tenants from a shared plant room, and charges for it, is a heat supplier under the Heat Network (Metering and Billing) Regulations 2014. On 27 January 2026 four of that role's old duties were removed in Great Britain: notifying the government, assessing whether metering is cost-effective, fitting heat cost allocators and following the billing regulation. The duties to meter, to keep meters accurate and to maintain them stayed. This guide sets out which is which, how communal heating differs from district heating, and what a tenant can and cannot do about leaving. Electricity sub-metering is a separate subject, covered in the sub-metering guide. The wider landlord picture is on the commercial landlord page.
What is communal heating, and how is it different from district heating?
The 2014 Regulations split the two by where the heat travels. Communal heating is the distribution of steam, hot water or chilled liquids from a central source in a building occupied by more than one final customer. A district heat network distributes the same thing through a network to multiple buildings or sites. Ofgem's registration rules use the same split: communal networks serve a single building divided into separate premises, and district networks serve two or more buildings.
The split matters for metering. A multi-occupier building fed by a district network needs a building-level meter, while the rule on meters for individual customers covers both communal and district supply. A multi-let office block heated from its own plant room is communal heating. The same block connected to a network that also serves its neighbours is supplied by a district heat network.
Is a landlord a heat supplier?
The metering duties fall on the heat supplier, defined as a person who supplies and charges for heating, cooling or hot water to a final customer through communal heating or a district heat network. A final customer is a person who buys heat for their own end consumption from a heat supplier. A landlord that meters tenants' heat use and bills them for it fits both definitions. A landlord that only recovers a share of boiler costs through a service charge may or may not, depending on how the lease and the charge are written. That is a question for a solicitor, not a guide.
Ofgem treats the landlord role as a separate point. Where the supplier is also the landlord for the property on the heat network, it says the supplier should follow both the authorisation conditions and relevant housing legislation. Ofgem describes a consumer as someone receiving heat from the network, such as a resident, tenant, leaseholder or bill payer.
Which parts of the 2014 rules were removed on 27 January 2026?
The Heat Networks (Market Framework) (Great Britain) (Amendment) Regulations 2026 (SI 2026/7) changed the 2014 Regulations for England, Wales and Scotland from 27 January 2026. DESNZ's guidance page, updated on 11 February 2026, adds that the department took over enforcement of what remains across Great Britain. The table shows each duty.
| Duty | 2014 provision | Position from 27 January 2026 |
|---|---|---|
| Notify the government of the network | Regulation 3 | Omitted |
| Cost-effectiveness assessment for existing buildings | Regulation 4(2B) to (2D) and (6) to (7A), Schedule 1 | Omitted |
| Heat cost allocators, thermostatic radiator valves and hot water meters | Regulation 6 | Omitted; regulation 8A ends any continuing duty |
| Minimum billing requirements | Regulation 9, Schedule 2 | Omitted |
| Building-level meter on a district supply | Regulation 4(1) and (2) | Still applies |
| Meters for individual customers | Regulation 4(2A), (3) and (4) | Still applies to the classes of building in regulation 2A |
| Temperature controls | Regulation 4(8) | Still applies |
| Meter accuracy, replacement and upkeep | Regulations 5, 7 and 8 | Still applies |
Northern Ireland is outside this change. DESNZ's page says the 2014 and 2020 obligations there are unaffected.
What metering must a heat supplier provide?
- A building meter where a district network feeds the building. Where heat comes from a district network to a building occupied by more than one final customer, the supplier must ensure meters measure it for that building. The meter sits at a heat exchanger in the building or at the point where the network pipes enter it.
- Meters for individual customers. Where a building supplied by district or communal heating has more than one final customer, the supplier must ensure sufficient meters are installed to measure each customer's consumption. The duty is tied to the viable class in regulation 2A. That class includes a building newly constructed for communal heating and connected from 1 September 2022, a building built for a district network and connected from 27 November 2020, and an existing district-supplied building that has major renovations to its technical services from that November date.
- Existing buildings outside those classes. DESNZ's page says meters must be installed if a cost-effectiveness assessment was positive before the 2026 amendment. A new assessment is no longer required.
- Temperature controls. Where individual meters are installed, the supplier must also ensure temperature control devices let each customer control its consumption.
Three standing duties apply once a meter is in place. A meter must accurately measure, memorise and display what each final customer consumes. A replacement meter must meet the same standard unless that would be technically impossible or the estimated cost would be unreasonable. And the supplier must, so far as possible, ensure meters are continuously operating correctly, properly maintained and periodically checked for errors. Failing to comply with the duties in regulations 4, 5, 7 or 8 is an offence, and conviction in England and Wales is punishable by a fine.
Where do the billing rules sit now?
Regulation 9 and Schedule 2, which set minimum billing requirements, were omitted for Great Britain from 27 January 2026. They were not replaced inside the 2014 set. Instead, the 2025 Market Framework Regulations let Ofgem attach conditions about billing to a network's authorisation, including requirements about the bills given to customers and about their frequency, accuracy and the use of estimates. Ofgem says its regulations focus on good outcomes for customers, including transparent, easy-to-understand energy bills. DESNZ's page confirms that from 27 January 2026 all heat networks in Great Britain are subject to Ofgem regulation.
Ofgem's consumer protection guidance is aimed mostly at domestic customers but includes some guidance on non-domestic supplier and operator requirements. A landlord that bills business tenants should read the authorisation conditions that apply to its role and that guidance, not the old Schedule 2. The redress route and the micro-business and small-business definitions are set out in the heat network regulation guide.
Can a business tenant opt out of communal heating?
No provision reviewed for this guide gives a customer a right to leave a communal system. The metering duties sit on the supplier, and a final customer is simply a person who buys heat from a heat supplier, so the relationship is contractual. The answer for a particular building is in the lease or the heat supply agreement. Look for a covenant requiring the tenant to take the landlord's heat, the landlord's right to change the system, and the basis on which heat is charged. A tenant that wants its own heating, such as a heat pump, will usually need to agree it with the landlord because one plant room serves the whole building.
What should a landlord do now?
- Map each supply. For every building, note whether heat arrives from a district network or from communal plant, who charges whom, and under which lease or contract.
- Check the meters. Confirm which buildings fall in the viable class, whether each customer has a meter that measures its consumption, and when the meters were last checked for errors. Keep the records.
- Retire the old billing template. Replace procedures built on Schedule 2 with ones that follow the Ofgem conditions for the landlord's role.
- Settle the Ofgem role. Operators and suppliers of relevant networks must give Ofgem details of their organisation, ownership, financial resilience and consumer protection arrangements by 26 January 2027.
- Look ahead. Zoning proposals in England could change which buildings are asked to connect, as the zoning guide explains.
Readers weighing options for a let building can send an enquiry through the form on this page, and the landlord page covers the other routes open to property owners.
Sources and last checked
- Legislation.gov.uk, checked 22 October 2026: regulation 2, 2A, 3, 4, 5, 6, 7, 8, 9, 11 and 13 of the Heat Network (Metering and Billing) Regulations 2014.
- Legislation.gov.uk, checked 22 October 2026: the 2026 amendment regulations (SI 2026/7) and the Heat Networks (Market Framework) (Great Britain) Regulations 2025.
- DESNZ, GOV.UK, checked 22 October 2026: Heat networks guidance, updated 11 February 2026.
- Ofgem, checked 22 October 2026: heat networks regulation, who should register, policy guidance and resources and consumer protection guidance, published 13 January 2026.
Guides on this topic
Common questions
Do I still have to notify anyone about my communal heating?
In Great Britain the duty to notify under regulation 3 of the 2014 Regulations was omitted on 27 January 2026. A separate duty applies under the Ofgem regime: operators and suppliers of relevant networks must give Ofgem details of their network by 26 January 2027. Northern Ireland is treated differently, and DESNZ's page says the 2014 and 2020 obligations there are unaffected.
Are heat cost allocators still required?
Not as a duty. Regulation 6 was omitted and regulation 8A says a supplier that was under that obligation is no longer under it. DESNZ's page adds that heat cost allocators can no longer be used to demonstrate compliance with the metering obligation, so a building that relies on them should check its position.
What is the penalty for failing to meter?
Failing to comply with the metering duties is an offence under regulation 11 of the 2014 Regulations. Conviction in England and Wales is punishable by a fine. DESNZ now enforces the duties that remain across Great Britain.
Is heat metering the same as electricity sub-metering?
No. The regulations in this guide cover heating, cooling and hot water supplied through communal or district systems. Metering a tenant's electricity follows different rules, which the sub-metering guide covers.