Variable Speed Drives: Where They Cut Motor, Fan and Pump Energy
Updated 23 October 2026 · Renewable Energy for Businesses
Want to cut what your site uses and pays for energy?
Request a quoteWhere do variable speed drives cut energy, and where do they not?
A variable speed drive (VSD) changes the speed of an AC motor by varying the supply frequency. CIBSE Journal says drives of this kind give speed reductions down to 20 per cent. They pay where the load asks for less than full output for many hours, and the clearest case is a fan or pump whose flow requirement moves up and down. Business Energy Scotland describes drives as matching the speed of pumps and fans to changing process requirements.
The reason is the fan relationship in CIBSE Journal's module on matching a fan to a ventilation system. The module treats fan diameter and air density as constant for a given fan and system, and gives this example: a 10 per cent increase in fan speed means a 10 per cent increase in air volume flow, a 21 per cent increase in pressure and a 33 per cent increase in power consumption. Power therefore moves roughly with the cube of speed. Run the other way, a small cut in speed removes a large share of power.
Compressors are a different case. The Carbon Trust's January 2012 compressed air release describes a company whose compressor remained on steadily even when it was not in use. Replacing it with a variable speed compressor cut that company's electricity use by 30 per cent. It is one example, and the cube relationship above is a fan relationship, so do not carry the figure over to other equipment.
Drives do little for motors that run flat out all day. CIBSE Journal puts drive conversion efficiency at typically above 96 per cent, so a drive on a motor that never slows only adds its own loss. It also warns that the imperfect output waveform may reduce peak motor efficiency by 1 or 2 per cent, and that motor efficiency may reduce significantly at speeds below 75 per cent. Where flow is currently held down by dampers, guide vanes or throttling, the same module says those methods are likely to severely reduce the potential savings available from reducing air volume, so they capture less of the saving than speed control does.
What does a fan at 80 per cent speed actually save?
The figures below are an illustration, not a quote. Assume a fan whose motor draws 10 kW at full speed for 4,000 hours a year, a system where the cube relationship holds, and a need for only 80 per cent of full flow. Cubing 0.8 gives 0.512, so the ideal power is 51.2 per cent of full-speed power. The last row allows for a drive at 96 per cent efficiency and a further 2 per cent motor loss, both taken from the CIBSE ranges above.
| Case | Power | Energy in 4,000 hours | Against full speed |
|---|---|---|---|
| Full speed | 10.0 kW | 40,000 kWh | Baseline |
| 80 per cent speed, ideal | 5.12 kW | 20,480 kWh | About 49 per cent less |
| 80 per cent speed, with drive and motor losses | About 5.4 kW | About 21,800 kWh | About 46 per cent less |
Real fans rarely sit at one speed. A second illustration uses the same ideal relationship across a load profile.
| Speed | Hours a year | Ideal power | Energy |
|---|---|---|---|
| 100 per cent | 1,000 | 10.00 kW | 10,000 kWh |
| 80 per cent | 2,000 | 5.12 kW | 10,240 kWh |
| 60 per cent | 1,000 | 2.16 kW | 2,160 kWh |
| Total | 4,000 | 22,400 kWh, 44 per cent below full speed all year |
The ideal figures are ceilings on what the fan relationship allows. They assume flow demand really is that low for those hours, and nothing in either table is a measured result.
How do you estimate savings from your own run hours and load profile?
- Measure the baseline. Log the motor's actual input power at the loads it sees, with any damper or vane in its normal position, not just the nameplate rating. The monitoring guide covers logging.
- Find the load profile. Count the hours the fan or pump needs each flow band, using the building management system, a flow meter or valve and damper positions.
- Apply the relationship band by band, as in the second table, then reduce the result for drive and motor losses.
- Check the system. CIBSE's simplified relationships assume a fixed fan and system with constant air density. For pumps, or fans against a fixed pressure, ask the designer to work from the fan or pump and system curves.
- Agree how the saving will be proved. BSI lists BS EN 17267, a plan for energy measurement and monitoring that supports the verification of savings, and ISO 50015 on measurement and verification of energy performance.
How do motor efficiency classes and the ecodesign rules fit in?
The ecodesign rules set a floor for the motor itself. Schedule 16 of the Ecodesign for Energy-Related Products and Energy Information Regulations 2021 says that from 1 July 2021 three-phase motors rated from 0.75 kW to 1,000 kW (with 2, 4, 6 or 8 poles, and not Ex eb increased safety types) must reach at least the IE3 efficiency level. Motors from 0.12 kW to below 0.75 kW must reach at least IE2. From 1 July 2023, three-phase motors of 75 kW to 200 kW with 2, 4 or 6 poles, other than brake and explosion-protected types, must reach IE4. Drives are covered too: from 1 July 2021 the power losses of VSDs rated for motors of 0.12 kW to 1,000 kW must not exceed the IE2 level.
Regulation 34 ties these to the moment a motor or drive is placed on the market or put into service, so they bear on what you buy. The regulation text does not itself say that installed motors must be replaced.
Class matters less than speed control when load varies. The Schedule's tables set minimum efficiencies for a 22 kW four-pole motor at 50 Hz of 91.6 per cent at IE2, 93.0 per cent at IE3 and 94.5 per cent at IE4. The step from IE2 to IE3 is 1.4 percentage points, while the 80 per cent speed illustration above removes about half the power. BSI's catalogue entry for BS EN IEC 60034-30-1:2026 (published 31 January 2026), the standard that defines the IE classes for single-speed motors, adds a limit: it does not cover the efficiency of power-drive systems, nor losses in cables, filters and frequency converters. A motor's class therefore says little about how it performs with a drive.
What can go wrong with a drive installation?
- Harmonics. CIBSE Journal lists inverters for speed controllers among the non-linear loads that distort the supply waveform.
- Power factor equipment. It says static power factor correction must not be applied at the output of a variable speed drive, soft starter or inverter, as it will damage the electronics. It adds that variable voltage, variable frequency drives give near unity power factor operation. The power factor guide covers reactive power charges.
- Low speeds. Motor efficiency may fall at lower speeds, so check the lowest speed the process will actually run at.
- Noise. CIBSE Journal says reducing fan speed is likely to reduce the noise emitted by the fan, which is a benefit for occupied spaces.
Drives are one step in a longer order of work, set out in the guide to cutting business energy costs. Readers who want help placing a drive project within a site plan can send an enquiry through the form on the energy management page.
Sources and last checked
Checked on 22 October 2026. The Carbon Trust motors and drives guide sits behind a download form, so only its landing page was read. The legislation and the standards bodies' pages are the authority if they disagree with this one.
- CIBSE Journal, Module 34: Matching the fan to the ventilation system (November 2011), checked 22 October 2026
- CIBSE Journal, Module 41: Power quality for building electrical supplies (June 2012), checked 22 October 2026
- Business Energy Scotland, case study page that describes drives on pumps and fans (undated), checked 22 October 2026
- Carbon Trust, How companies can save money from thin air (25 January 2012), checked 22 October 2026
- Carbon Trust, Motors and drives technology overview guide (May 2018, landing page), checked 22 October 2026
- legislation.gov.uk, Ecodesign for Energy-Related Products and Energy Information Regulations 2021, Schedule 16 and regulation 34, as made, checked 22 October 2026
- BSI, BS EN IEC 60034-30-1:2026 (31 January 2026), BS EN 17267:2019 (30 September 2019) and ISO 50015:2014 (11 December 2014) catalogue pages, checked 22 October 2026
Common questions
Do the ecodesign rules make me replace motors I already have?
Regulation 34 of the 2021 Regulations says a motor or variable speed drive must conform when it is placed on the market or put into service. The regulation text does not itself require installed motors to be replaced. The rules bear on new purchases and replacements, so ask your supplier which class a quote meets.
How slowly can a fan run on a drive?
CIBSE Journal says drives of this kind give speed reductions down to 20 per cent, but warns that motor efficiency may fall significantly below 75 per cent speed. The lowest practical speed depends on the process, the minimum airflow it needs and what the manufacturer allows.
Does a drive suit a compressor?
It can where demand varies. The Carbon Trust's 2012 example was a compressor that stayed on even when idle, replaced with a variable speed unit that used 30 per cent less electricity at that company. The fan relationship in this guide does not apply to compressors, so judge the case on the site's own demand profile.