Thermal Energy Storage for Business: Storing Heat and Cold to Shift Energy Use
Updated 10 November 2026 · Renewable Energy for Businesses
Weighing up a heat pump or other low-carbon heating?
Request a quoteMany businesses already store heat without calling it that: a hot water cylinder is a thermal store. Scaled up and controlled, the same idea lets a hotel, food producer, office or factory separate when it buys electricity from when it needs heat or cold. This guide covers how stores work, which types suit a business, why they change costs, how they compare with storing electricity, the rules that apply and how to test the idea with a site's own data.
How does thermal energy storage work?
A 2016 evidence review for the government describes thermal energy storage as keeping energy as heat or coolth for later heating, cooling or power generation, and sorts it into three families:
- Sensible storage raises or lowers the temperature of a solid or liquid without changing its state, as in a hot water tank. The review calls it by far the most established type.
- Latent storage uses phase change materials (PCMs), such as ice, which take in or give out heat as they melt or freeze at a set temperature.
- Thermochemical storage uses reversible chemical reactions to hold large amounts of heat in a compact volume.
Stores run from hours to seasons. The review says tanks usually store heat within the day, while large tanks, boreholes, pits and aquifers have all been demonstrated carrying heat between seasons.
Which types of thermal store suit a business?
The table draws on the 2016 review, the June 2025 innovation needs assessment for heat and buildings that DESNZ commissioned, and the Environment Agency's March 2025 report on energy storage. Temperatures appear only where a source gives them.
| Store | What it holds | Temperatures in the sources | Business use | Check |
|---|---|---|---|---|
| Hot water tank | Hot water for heating or taps | Water for outlets stored at 60°C or more (HSE) | Hotels, care homes, leisure, offices | Space, insulation, legionella controls |
| Chilled water or ice | Cold, as chilled water or ice | Not given | Building cooling shifted from peak to off-peak hours | Fit with the chillers and controls |
| Other phase change materials | Heat or cold at a set melting point | Materials exist from freezing to high temperatures | Tight spaces needing a steady temperature | Narrow working range, cost |
| High-temperature solids or molten salt | Heat in concrete, rock or salt | Not given | Process heat; see the process heat guide | Pressure rules if it raises steam |
| Thermochemical | Heat as chemical energy | Not given; readiness level 5 to 8 | Mostly pilots so far | Proven performance |
| Aquifer or borehole | Heat or cold in the ground | Low-temperature aquifer stores inject below 25°C; high-temperature ones above 50°C | Offices and shopping centres | Environment Agency consents |
The assessment describes sensible stores of water, molten salt and concrete as mature and widely used in domestic and industrial applications, and picks out ice-water storage for uses needing stable temperatures, such as shifting building cooling to off-peak times. The 2016 review adds that PCM cooling applications are more advanced than PCM heat storage, and that a PCM's narrow temperature range makes sensible storage more economical where a wider range is acceptable. Some underground stores are still at trial stage: in a trial completed in early 2026, the Mining Remediation Authority stored 98 MWh of heat in old mine workings in Glasgow over 25 days, at up to 32°C, with the data due in 2027.
On heat networks. Research for DESNZ published on 11 August 2025 found UK networks mainly use short-duration tanks for peak shaving and resilience, and no operational large-scale interseasonal store in the UK, unlike Denmark and the Netherlands. On networks led by combined heat and power, storage has been proven to optimise engine operation and cut the need for peak plant; on electrically driven ones it can widen access to cheaper off-peak electricity, a benefit not yet fully realised in the UK. Land costs, space and fragmented ownership were the main barriers, and the Clean Flexibility Roadmap's July 2026 update says the research found significant potential to increase grid flexibility and reduce bills. The guide to what a heat network is explains how networks work.
Why can storing heat or cold cut costs and carbon?
Price. The 2025 assessment says thermal stores can charge in off-peak hours, when electricity demand and prices are lower, and release the energy at peak. That needs a tariff that varies by time of day; the time-of-use tariffs guide explains those tariffs and how half-hourly settlement is spreading them. The simplest version is an electric boiler charging a hot water store, which the electric boiler guide covers. A heat pump can charge a store in the same way, and the commercial heat pump page covers that equipment at business scale.
Capacity. The same assessment says thermal storage can reduce peak load on the electricity grid. On a site close to its agreed supply capacity, a store lets electric heating or cooling plant charge outside the busiest hours instead of adding to the peak.
Carbon. NESO's carbon intensity service says the carbon intensity of electricity varies by hour, day and season with demand and the mix of low-carbon and conventional generation, so moving consumption can cut emissions as well as cost. The Warm Homes Plan expects heat networks to use large-scale thermal storage in the same way, generating heat in lower-cost, lower-carbon periods.
Is it better to store heat or electricity?
A thermal store holds energy in the form the site will use, so it can only serve heating or cooling. A battery stores electricity, which can serve any load on site, and the battery storage guide shows how a business battery earns its keep. Three practical differences follow for a thermal store:
- Losses. The Environment Agency's report says heat loss from a tank store depends on its surface area, the temperature difference with its surroundings and its insulation, so a compact, well-insulated store kept near its use temperature loses least.
- Space. Water stores are bulky, and the heat network research for DESNZ names land costs and limited space as major barriers. The 2016 review says PCMs can beat sensible stores on energy density, store volume and losses where the use needs a narrow temperature range.
- Duration. Thermochemical stores hold energy in chemical bonds with minimal thermal losses, the 2025 assessment says, but they are not yet a mainstream product.
Which rules apply to a thermal store?
Pressure. HSE's guidance on the Pressure Systems Safety Regulations 2000 covers systems holding a relevant fluid, which includes steam at any pressure and pressurised hot water above 110°C. Before such equipment is used, a written scheme of examination must be in place and an examination carried out, so a store that raises steam or holds water above that temperature is in scope.
Legionella. HSE says hot water should be stored at 60°C at least to kill legionella bacteria, and its Approved Code of Practice L8 sets duties including assessing the risk, a control scheme, monitoring and record keeping, and appointing a responsible person. A store that feeds taps or showers has to be run with that in mind.
Aquifer stores. These pump groundwater, so in England the Environment Agency's open-loop rules apply: groundwater investigation consent before drilling, an abstraction licence above 20 cubic metres a day, and a discharge permit or registered exemption. The exemption covers cooled aquifer systems under 1,500, balanced systems under 430 and heated systems under 215 cubic metres a day, and a system that can reverse its flow needs consent for every borehole.
How can a site test whether thermal storage would pay?
- Get twelve months of half-hourly electricity data and, where possible, metered heat or cooling demand. Where heat is not metered, gas use or plant run hours give a rough profile.
- Lay the demand for heat or cold, hour by hour, against the tariff bands and the site's spare supply capacity.
- Choose the hours the store must cover and the energy it must hold, in kWh of heat or cold.
- Check the temperature the use needs, including the legionella limit for hot water outlets.
- Check space, floor loading and access for a store of that size, with the designer converting kWh into volume.
- Price the shift with the tariff test in the time-of-use guide, after allowing for standing losses.
- Check the pressure, legionella and groundwater rules, then compare the result with doing nothing.
For example, a hypothetical hotel uses 500 kWh of heat a day for hot water, 300 kWh of it between 6am and 10am. A store holding 300 kWh, charged overnight, would move that heat out of the morning; if the store lost 10% of its heat a day, the plant would have to put in about 333 kWh to deliver it. The numbers are illustrations, not sourced figures. Readers weighing the option for a site can send an enquiry through the form on this page.
Sources
All pages checked 10 November 2026; the official pages are the authority if they differ.
- DESNZ and BEIS, GOV.UK: Evidence gathering: thermal energy storage technologies (16 November 2016); Energy Innovation Needs Assessment: heating and buildings (June 2025); Exploring the take-up and usage of thermal energy storage in heat networks (11 August 2025); Clean flexibility roadmap: July 2026 update (13 July 2026); Warm Homes Plan (21 January 2026)
- Environment Agency, GOV.UK: Environmental and social implications of energy storage technologies (14 March 2025); Open loop systems: apply to install one (updated 23 February 2026)
- HSE: Pressure Systems Safety Regulations 2000; Hot and cold water systems: things to consider; L8 Approved Code of Practice
- NESO: Carbon Intensity API; National carbon intensity forecast
- Mining Remediation Authority, GOV.UK: Mine water heat (updated 7 October 2026)
Common questions
Is a hot water cylinder a thermal store?
Yes. The 2016 government review counts hot water tanks as sensible heat storage, the most established type. What changes at business scale is the size, insulation and controls, so the tank can be charged at chosen times.
Can thermal storage pay without a time-of-use tariff?
Less often. A store can still help a site stay within its supply capacity, but most of the cost case comes from buying electricity in cheaper hours, and without that price gap the store's standing losses are simply a cost.
What is aquifer thermal energy storage?
It keeps heat or cold in groundwater, pumped between warm and cold wells. The Environment Agency's 2025 report says lower-temperature systems typically inject water below 25°C and are often used in larger complexes such as office buildings and shopping centres.
Can old mine workings store heat?
Possibly. In a trial in Glasgow, completed in early 2026, the Mining Remediation Authority stored 98 MWh of heat in mine workings at up to 32°C. It is research with data due in 2027, not yet a service a business can buy.